After-sales Service: | Response on Customers′ Questions Within 12 Hours. |
---|---|
Warranty: | 365 Days |
Description: | IEC62771 Digital Automatic Circuit Breaker Tester |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Item Name | CBA-III IEC62771 Digital Display Automatic High Voltage Circuit Breaker Tester |
1 | 12 channels for time measurement | 3-channel support both the time contact and resistance contact time 6-channel isolated contacts for cascaded unit measurement of pole |
2 | Time measurement | Range: 4000ms; Error :< 0.1ms; Resolution: 0.01ms |
3 | Travel measurement according to sensor | Linear resistance sensor: Measurement range: 0~250mm; resolution: 0.01mm; error: <0.5mm Measurement range: 0~25mm; resolution: 0.01mm; error: <0.05mm Angle resistance sensor: Measurement range: 0~360°; resolution: 0.01°; error: <0.5° |
4 | Pre-insertion resistance measurement | Range: 50~5000ohm; error :<1%RDG+2D |
5 | Dynamic resistance measurement | Test current: 25~100A, Measurement error :< 1%RDG+2D |
6 | Contact resistance measurement | Range:0--10mohm, Error <0.5%RDG+0.05%FS Range: 0-2mohm, Error: <0.5%RDG+2D |
7 | Speed measurement | 250mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D 25mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D Angle sensor: 0~20m/s; error: <0.5%RDG+2D Acceleration sensor: 0~20m/s; error: <5%RDG+2D |
8 | Coil current measurement | Range: 0~20A; resolution: 0.001A; error: <0.01A |
9 | Vibration measurement | Range: 0~5000G; error: <3% |
10 | Internal DC power source | voltage: 12~265V; current:0~20A |
11 | Data transaction | Builtin 8G storage memory and 2 USB interface for data export and external keyboard or mouse connection |
12 | Power supply | AC220V±10%; 50Hz±10% |
13 | Working environment | -10~50°C; Humidity: <80% |
Comparing with the traditional circuit breaker tester, this Circuit Breaker Analyzer has the following unique advantages:
The integrated vibration test function of Circuit Breaker Analyzer provides a new means of detection circuit breaker mechanical characteristics for users, compared to traditional time measurement and speed measurement, the vibration fingerprint detection is easier and more efficient.
The vibration fingerprint test results contain richer information of circuit breaker operation, for potential risk of failure or faulty breakers, it can locate the fault position quickly.
The vibration tests do not need to change the original line connection, so the users can complete the charged detection of mechanical characteristics of circuit breaker.
Arcing contact analysis module allows users to automatically assess the degree of loss of inside Arc suppression contact of circuit breaker without disassembly.
Users can use CBA-III Circuit Breaker Tester to complete the contact resistance tests, do not need to buy contact resistance tester separately.
Measurement of closing time, opening time, time spread between poles, time spread between units of one pole, bounces etc.
Measurement of closing speed, opening speed and average speed.
Measurement of clearance between open contacts, over travel, overshoot travel and total travel.
Measurement of closing coil current time curve, opening coil current time curve and the maximum coil current
Test travel time curve, speed time curve and acceleration time curve
Measurement of pre-insertion resistance value and pre-insertion ion time.
Test contact resistance
Measurement of dynamic resistance time curve and length for arcing contacts
Vibration test, including vibration fingerprint curve acquisition, management, and vibration fingerprint curve automatic matching.
CO-t1-CO,O-t-CO-t1-CO,CO rated operating sequence verification test.
Drawing Envelopes for reference travel curve and compare travel curve with envelopes
Mechanical travel curve automatic compare with saved travel curve
Measurement of CO time (close-open time) and OC time (Opening-Closing time)
Graphite contact closing time, opening time, dynamic resistance curve measurement
Zoom, editors, statistics and analysis for measurement curves.
12.1-inch touch screen for control and data input Built-in micro printer for test result printout.
Generate WORD format test report automatically (all reports and data can be exported through Flash disk).