JF-2004 Handheld Ultrasonic PD Detector Partial Discharge Tester
Product Description
JF-2004 Handheld Ultrasonic PD Detector Partial Discharge Tester is used for the detection and evaluation of the insulation status of high-voltage switchgear, ring network cabinets, transformers, GIS, overhead lines, cable terminals, cable branch boxes and other equipment.
Partial discharge intensity detection: By measuring the discharge signal within a power frequency period, the intensity of partial discharge is characterized according to the maximum value (dB) in the discharge pulse sequence.
Partial discharge frequency detection: The device measures the discharge signal within a power frequency period, extracts discharge pulses and characterizes the frequency of partial discharges according to the number of discharge pulses.
Application Field
Development and distribution enterprises
Railway system
Petrochemical power supply system
Aerospace testing field
Automatic testing field
Product Parameters
TEV measurement |
UHF measurement |
Measuring range |
0-60 dBmV |
detection frequency |
300-2000MHz |
Resolution |
1dB |
measurement range |
0-60 dBmV |
Accuracy |
±1dB |
accuracy |
<1dBmV |
Maximum pulse per cycle |
1400 |
Sensor band |
300-2000MHz |
Measurement frequency band |
3~100MHz |
|
|
AA measurement |
AE measurement |
Measuring range |
-6dBμV - 68dBμV |
Measuring range |
-6dBμV - 68dBμV |
Resolution |
1dB |
Resolution |
1dB |
Accuracy |
±1dB |
Accuracy |
±1dB |
Sensor center frequency |
40 kHz |
Frequency range |
20~200 kHz |
HFCT measurement |
Sensor transmission impedance |
5mV/mA |
Detection frequency |
1~30MHz |
Sensitivity |
≤50pC |
Hardware |
Shell |
ABS |
Display |
4.0 inch RGB LCD screen |
Controller |
ARM |
Connector |
USB interface (also charger input) 3.5mm stereo headphone jack External ultrasonic sensor input wireless wifi Wireless synchronization benchmark |
Earphone |
minimum 8 ohm |
SD card |
standard 16G |
Built-in battery |
3.7V/1Ah lithium battery |
Working time |
about 8 hours |
Charger |
AC 90-264V or DC 5V |
Operating temperature |
-20 ~ 50ºC |
Humidity |
20-85% relative humidity |
Weight |
0.4KG(host) |
Features
-
Configure different sensors to realize partial discharge detection of almost all electrical equipment;
Humanized man-machine interface facilitates data management of different devices, including traceback of historical data change trends, horizontal and vertical data analysis, and realizes 360 ° comprehensive diagnosis of the device under test;
Built-in ultrasonic sensors and transient ground voltage (hereinafter referred to as TEV) sensors, which can be connected with special sensors such as transformers, GIS, overhead lines and cables;
Adopt non-intrusive detection method, no power failure during the test, maybe no high voltage source is applied, which is more convenient to use than traditional pulsed partial discharge detector;
The test bandwidth range is 30kHz ~ 2.0GHz, suitable for the detection principle of various frequency bands;