Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply: AC220V±10%, 50/60Hz±10%
Voltage output: 0.1~180V (AC)
Current output: 0.001~5A(RMS)
Power output: 500VA
Maximum knee voltage measurement: 45KV
PT ratio error measurement: typical error <0.05%, maximum error<0.1%
PT phase angle measurement: maximum error < 3min
Memory capacity: >1000 groups test results
Working condition: temperature: -10ºC~50ºC, humidty: ≤90%
Size: 485mm * 356mm * 183mm, weight: <15kg
Test Parameters | Range | Error | Resolution |
Current | 0~10A (automatically change range in 0.1/0.4/2/10A) | <±0.1%+0.01%FS | / |
Voltage | 0~200V (automatically change range in 1V/10V/70V/200V) |
<±0.1%+0.01%FS | / |
Turns Ratio | 1~5000 | <0.05% | / |
5000~35000 | <0.1% | / | |
Phase | / | ±2min | Resolution: 0.01min |
Winding Resistance | 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) | <0.2%RDG+0.02%FS | Max. resolution: 0.1mΩ |
Temperature | -50~100 Celsius degree | <3 Celsius degree | / |
CT Secondary Burden | 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) |
<0.2%RDG+0.02%FS | Max. resolution: 0.001ohm |
PT Secondary Burden | 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) |
<0.2%RDG+0.02%FS | Max. resolution: 0.1ohm |
PT Ratio | 1~10000 | <0.1% | / |
10000~35000 | <0.2% | / |
Make evaluation for test results according to selected standards.
Make word report for test result.
Make word reports one time for multi-group test records on the PC.
Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test.
Compare excitation curves with saved excitation curves in the same window.