After-sales Service: | Online Training, Reply Customer′s Question in 12h |
---|---|
Warranty: | 12 Months |
Test Standards: | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5 |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CPT-III Automatic CT PT Analyzer is used to measure all kinds of current transformers and voltage transformers.
CPT-III Automatic CT PT Analyzer can calculate the ratio errors and phase angle errors of the current transformer and voltage transformer at the rated burden and working burden in one test.
CPT-III Automatic CT PT Analyzer can automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.
Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply: AC220V±10%, 50/60Hz±10%
Voltage output: 0.1~180V (AC)
Current output: 0.001~5A(RMS)
Power output: 500VA
Maximum knee voltage measurement: 45KV
PT ratio error measurement: typical error <0.05%, maximum error<0.1%
PT phase angle measurement: maximum error < 3min
Memory capacity: >1000 groups test results
Working condition: temperature: -10ºC~50ºC, humidity: ≤90%
Size: 485mm * 356mm * 183mm, weight: <15kg
Test Parameters | Range | Error | Resolution |
Current | 0~10A (automatically change range in 0.1/0.4/2/10A) | <±0.1%+0.01%FS | / |
Voltage | 0~200V (automatically change range in 1V/10V/70V/200V) |
<±0.1%+0.01%FS | / |
Turns Ratio | 1~5000 | <0.05% | / |
5000~35000 | <0.1% | / | |
Phase | / | ±2min | Resolution: 0.01min |
Winding Resistance | 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) | <0.2%RDG+0.02%FS | Max. resolution: 0.1mΩ |
Temperature | -50~100 Celsius degree | <3 Celsius degree | / |
CT Secondary Burden | 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) |
<0.2%RDG+0.02%FS | Max. resolution: 0.001ohm |
PT Secondary Burden | 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) |
<0.2%RDG+0.02%FS | Max. resolution: 0.1ohm |
PT Ratio | 1~10000 | <0.1% | / |
10000~35000 | <0.2% | / |
Evaluate test results according to selected standards.
Make a word report for the test results.
Make word reports one time for multi-group test records on the PC.
Calculate the ratio errors and phase angle errors at the rated burden and working burden in one-time test.
Compare excitation curves with saved excitation curves in the same window.