PRT-PC3 China Best Price Single Phase Secondary Current Injection Tester 3 Three Phase Protection Relay Test Kit is applied to test the relay unit in relay protection system.
At the same time it could be considered as a universal three phase AC/DC voltage source or current source.
PRT-PC3 S is applied to test protection replay based on voltage and current operation.
The main function of the tester include: calibration of voltage and current operation relays, secondary circuit inspection, trip value of circuit breaker test, switch on and off time measurement of circuit breaker and so on.
It's a low cost, simple operation and reliable performance device for secondary circuit test.
AC current output | |
Phase current output (effective value) 0~40A | Output precision 0.2 degree |
3 phase parallel current output (effective value) | 0~120A |
A long-time phase current | 10A |
Maximum output power of phase current | 420VA |
Maximum output power of 3 parallel current | 900VA |
Maximum permitted work time of 3 parallel current | 10s |
Frequency range ( fundamental) | 20~1000Hz |
Harmonic time | 1~20 |
DC current output | |
Current output | 0~±10A / phase, 0~±30A / 3 parallel |
Output precision | 0.5 degree |
AC voltage output | |
Phase voltage output (effective value) 0~120V | Output precision 0.2 degree |
Line voltage output (effective value) | 0~240V |
Phase voltage / Line phase output power | 80VA / 100VA |
Frequency range (fundamental) | 20~1000Hz |
Harmonic time | 1~20 |
DC voltage output | |
Phase voltage output range 0~±160V | Output precision 0.5 degree |
Line voltage output range | 0~±320V |
Phase voltage / Line phase output power | 70VA / 140VA |
10 path digital input and 8 path digital output | |
Time measuring range 0.1ms ~ 9999s | Accuracy of measurement <0.1ms |
Volume & weight | 400×360×160mm³ ,18kg |
Environmental temperature | -10°C~+50°C |