Protection Relay Testers for Choice:

PRT-PC6 Computer Control Six-Phase Protection Relay Tester
Product Description
RPT-PC6 Six Phase Protection Relay Tester with standard 6 phase voltage and 6 phase current output, voltage 125V/phase, current 30A/phase, 6 phases in parallel can up to 180A.
With digital Signal Processor Microcomputer, it can not only test the traditional relays and protectors but also can test the modern microcomputer relays, especially for transformer differential protection and transfer equipment testing.
Features
Classic Windows XP operating interface, 8.4-inch resolution of 800*600 TFT true color display.
Equipped with an ultra-thin industrial keyboard and optical mouse, complete a variety of operations using the keyboard or mouse the same as an ordinary PC.
The main control board is DSP + FPGA architecture, 16-bit DAC output, generates high-density sine wave 2000 points each circle to fundamental wave, which greatly improves the wave quality and the accuracy of the test instrument.
Using high-fidelity linear amplifier. Both to ensure the accuracy of a low current and also to guarantee the stability of a high current.
USB directly connects to the PC, without any adapter cable, easy to use.
It can be connected to a laptop computer (optional). Laptop computers and industrial machines use the same software, there is no need to re-learn the methods of operation.
With a separate DC auxiliary voltage source, output voltage 110V(1A), and 220V(0.6A), provide relays or protective devices that require DC power.
The software with a self-calibrating function, which avoids calibrating accuracy by adjusting relays after opening the case, greatly improves the stability of the accuracy.
Functions
RPT-PC6 Relay Tester is suitable for the following relays and protection devices testing:
Relay test |
Microprocessor-based protection device line protection |
Generator transformer protection |
Others |
Signal relay |
Multi-stage over-current |
Differential protection |
Automatic synchronizing device |
Time relay |
Over (less) voltage |
Field loss protection |
Protection device |
Intermediate relay |
Sequence components voltage and current |
Excitation protection |
Bus bar differential protection |
Reclosing relay |
Frequency devices |
Composite voltage locking ( direction) over-current (Reserve) |
Fiber-optic lines differential protection |
Current relay |
Power directional protection |
|
|
Over (less) voltage relay |
Reclosing and conversion failure |
|
|
Sequence component relay |
Distance and zero sequence |
|
|
Synchronism-check (or phase comparison) relay |
Power frequency variation distance |
|
|
Extremely inverse current relay |
Composite voltage |
|
|
Differential relay |
Locking (direction) Current |
|
|
Power (direction) relay |
Low cycle, low voltage load shedding device |
|
|
Impedance relay |
|
|
|
Synchronous relay |
|
|
|
Frequency relay |
|
|
|
Product Parameters
No. |
Item Name |
RPT-PC6 Secondary Current Injection Tester |
1 |
AC current source |
|
Current Range |
6x (0~30A)/phase |
Current accuracy |
0.5% |
6-phase parallel curr
ent output |
180A |
Phase current working value for allowed long time |
10A |
Power |
300VA/phase |
Max. output power of 6 phases in parallel |
900VA |
Max. permitted work time of 6 phases in parallel |
10S |
Frequency range |
0~1000Hz; accuracy: 0.001Hz |
2 |
DC current source |
|
Current Range |
20A / phase |
power |
300VA/phase |
accuracy |
0.5% |
3 |
AC voltage source |
|
Phase voltage output |
6x( 0~125V)/phase |
accuracy |
0.5% |
Line voltage output |
0~250V |
Phase voltage / Line voltage output power |
70VA / 100VA |
Frequency range |
0~1000Hz |
Frequency accuracy |
0.001Hz |
4 |
DC voltage source |
|
Phase voltage output range |
0~±150V |
accuracy |
0.5% |
Line voltage output range |
0~±300V |
Phase voltage / Line voltage output power |
90VA / 180VA |
5 |
Switch terminal |
|
Switch input terminals |
8 pairs |
Dead contact |
1-20mA, 24V ac |
Potential flip |
- -6V DC low level 15-250V DC high level
|
Switch output terminals |
4 pairs, dead contact, rupturing capacity: 110V/2A, 220V/1A |
6 |
Time measurement range |
|
Range |
1ms-9999s |
Accuracy |
1ms |
7 |
Dimension & weight |
|
Dimension |
455 (mm)×530 (mm)×220 (mm) |
Weight |
30kg |
8 |
Power |
AC220V±10%, 50Hz, 15A |