After-sales Service: | Online Training, Reply Customer′s Question in 12h |
---|---|
Warranty: | One Year |
Output Voltage: | 10kv or 12kv |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
TDT Three Phase Transformer Power Factor Tester 12kV is used to measure electrical loss tangent and capacitance of all kinds of high voltage electrical equipment in power plants, substations, laboratory, etc.
TDT Three Phase Transformer Power Factor Tester 12kV is composed of a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor, it is integrated structure.
It can also supply high voltage source for testing.
Frequency can be changed to 50Hz, 47.5Hz\52.5Hz, 45Hz\55Hz, 60Hz, 57.5Hz\62.5Hz, 55Hz\65Hz; thus, it can avoid interference of power frequency.
No. | Item Name | TDT Three Phase Transformer Power Factor Tester 12kV | |
1 | Output | 0.5KV∽10KV | Every 0.1kV |
Precision | 2% | ||
Maximum current | 200mA | ||
Capacity | 2000VA | ||
2 | Self-excited power | AC 0V∽50V/15A | 45HZ/55HZ 47.5HZ/52.5Hz/55HZ/65HZ 57.5HZ/62.5H Automatic double frequency |
3 | Resolving power | tgδ: 0.001% | Cx: 0.001pF |
4 | Precision | △tgδ:±(Reading*1.0%+0.040%) △C x :±(Reading*1.0%+1.00PF) | |
5 | Measuring range | tgδ | Unlimited |
C x | 15pF < Cx < 300nF | ||
10KV | Cx < 60 nF | ||
5KV | Cx < 150 nF | ||
1KV | Cx < 300 nF | ||
CVT test | Cx < 300 nF | ||
6 | CVT range | 10∽10000 | Accuracy: 0.1% |
7 | Dimension | 350mm*270mm*270mm | |
8 | Weight | 28kg | |
9 | Working enviorment | -15ºC∽40ºC, RH<80% | |
10 | Anti-interference | Frequency conversion | |
11 | Power Supply | AC 220V±10%, 50Hz |
TDT used in the Philippines: