KFZ Transformer Load Tester, Load Loss, No Load Loss Testing Equipment
Product Description
KFZ Transformer Load Tester, Load Loss, No Load Loss Testing Equipment is designed for transformer capacity, load loss and no load loss testing.
KFZ Transformer Load Tester, Load Loss, No Load Loss Testing Equipment can measure following parameters of transformer: capacity, transformer type, no-load current, no-load loss, short circuit (load) loss and impedance voltage.
Power Transformer Parameters Testing Transformer Capacity Tester is reliable, accurate, simple for wiring and operation.
Product Parameters
| No. |
Item Name |
KFZ Transformer Load Tester, Load Loss, No Load Loss Testing Equipment |
| 1 |
Test Parameters |
Transformer capacity, no-load current, no-load loss, short circuit voltage, short circuit (load) loss |
| 2 |
Working power |
Input voltage |
185Vac~250Vac |
| Allowable input voltage |
85Vac~264Vac |
| Frequency |
50/60Hz |
| Allowable frequency |
45Hz~65Hz |
| Input power |
40VA |
| 3 |
AC voltage |
Range |
10~650V |
| Resolution |
0.001V |
| Accuracy |
0.2%±0.001V |
| 4 |
AC Current |
Range |
0.5~60A |
| Resolution |
0.001A |
| Accuracy |
0.2%±0.001A |
| 5 |
Frequency |
Range |
45Hz~65Hz |
| Resolution |
0.001Hz |
| Accuracy |
0.2%±0.001Hz |
| 6 |
Power |
Range |
0~39kW |
| Resolution |
0.001kW |
| Accuracy |
<±0.5%(CosΦ>0.1) ±1.0%(0.02<CosΦ<0.1) |
| 7 |
Capacity test range |
10kV Dry type transformer |
30kVA~3150kVA |
| 10kV Oil immersed transformer |
30kVA~3150kVA |
| 35kV Oil immersed transformer |
50kVA~31500kVA |
| 20kV Dry type transformer |
50kVA~2500kVA |
| 35kV Dry type transformer |
50kVA~2000kVA |
| 8 |
Environment |
Operating temperature |
-10ºC~+50ºC |
| Storage temperature |
-25ºC~+70ºC |
| Relative humidity |
5%~95% |
| 9 |
Dimension |
40cm*30cm*22cm |
| 10 |
Weight |
≈8kg (Excluding accessories) |
Features
- Measurement range of voltage, current and capacity is wide, and measurement range can convert automatically. For example, the instrument can complete load test under full current of distribution transformer below 1000kVA. The load test of distribution transformers below 3150kV can be completed under 1/3 of the rated current (under 1/3 rated current, the instrument can be converted to the load loss parameter under the rated current).
- When testing load and no load loss of three phase transformer, it can automatically determine whether the wiring is correct or not, and display vector of three phase voltage and current.
- All test results can be automatically corrected. LCD 20 * 240 large screen.
- Users can preset 40 sets sample parameters, and these parameters can be deleted or added at any time.
- With real-time electronic clock, which can automatically record test date and time.
- 500 sets test data can be stored in the tester, meanwhile, users can connect the tester with computer to upload the data.
- With built-in printer, users can print test result immediately after test.
- Allows external current transformers or voltage transformers to extend measurement range, so it can test any kinds of transformers.
Detailed Photos
Packaging & Shipping
The whole set of KFZ Transformer Load Tester, Load Loss, No Load Loss Testing Equipment is packed in one veneer case.
Packing dimension: 55cm * 45cm * 40cm;
Total weight: 18kg
It is suitable for shipping by Express.
Our Advantages
1. High Quality Product: Most equipment have been on sale for more than 10 years, they are stable, reliable, with high quality and good reputation. All the products have been tested, run well and adjusted to good condition before delivery.
2. Good Faith Cooperation: Honesty is our foundation, we don't brag about the company and products, seek truth from facts, and don't make random promises.
3. Innovative Technology: Based on full experience in designing and manufacturing these equipment, and with users' feedback, we continuously improving our equipment and developing new products.
4. Awesome Service: Provide professional advice and reasonable offers within 2 hours at working time, and within 12 hours at non-working time. One year warranty for all the products, life time technical consulting, life time provision of spare parts, free software upgrades.

After Sales Service
1. Warranty period for all products is One year;
2. Within warranty period, all quality problems of the instrument shall be repaired by our company free of charge;
3. Beyond warranty period, our company shall be responsible for life-time maintenance, only the cost of the accessories will be charged;
4. User manual will be sent with the tester, some testers have demo for review.
5. If users have question on operation, we supply on-line video training. Users can also come to our factory to get free training.