After-sales Service: | Online Training for Operation and Installation |
---|---|
Warranty: | 365 Days |
Description: | Automatic Multifunctional CT Tester |
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
CPT-III Transformer CT Tester is used to measure all kinds of current transformer and voltage transformer.
CPT-III Transformer CT Tester can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one test.
CPT-III CT Testercan automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.
Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply: AC220V±10%, 50/60Hz±10%
Voltage output: 0.1~180V (AC)
Current output: 0.001~5A(RMS)
Power output: 500VA
Maximum knee voltage measurement: 45KV
PT ratio error measurement: typical error <0.05%, maximum error<0.1%
PT phase angle measurement: maximum error < 3min
Memory capacity: >1000 groups test results
Working condition: temperature: -10ºC~50ºC, humidty: ≤90%
Size: 485mm * 356mm * 183mm, weight: <15kg
Test Parameters | Range | Error | Resolution |
Current | 0~10A (automatically change range in 0.1/0.4/2/10A) | <±0.1%+0.01%FS | / |
Voltage | 0~200V (automatically change range in 1V/10V/70V/200V) |
<±0.1%+0.01%FS | / |
Turns Ratio | 1~5000 | <0.05% | / |
5000~35000 | <0.1% | / | |
Phase | / | ±2min | Resolution: 0.01min |
Winding Resistance | 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) | <0.2%RDG+0.02%FS | Max. resolution: 0.1mΩ |
Temperature | -50~100 Celsius degree | <3 Celsius degree | / |
CT Secondary Burden | 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) |
<0.2%RDG+0.02%FS | Max. resolution: 0.001ohm |
PT Secondary Burden | 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) |
<0.2%RDG+0.02%FS | Max. resolution: 0.1ohm |
PT Ratio | 1~10000 | <0.1% | / |
10000~35000 | <0.2% | / |
Make evaluation for test results according to selected standards.
Make word report for test result.
Make word reports one time for multi-group test records on the PC.
Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test.
Compare excitation curves with saved excitation curves in the same window.
Suppliers with verified business licenses